CERTIFICATE OF COMPLIANCE
Certificate Number | INTL-202204-C01 | Project Number: | INTL-202204-C01 |
---|---|---|---|
Date Issued: | June 27, 2022 | Client Number: | INTL-202204 |
Certification System: | Type 3 (ISO/IEC Guide 67) | Issued to: | Curtiss-Wright Nuclear Canada 165 Pony Drive Newmarket, ON L3Y 7B5 Canada |
Certification Body: | International Testing Laboratory Inc. | Issued By: | Certification Manager |
The products listed below are eligible to bear the INTL Certification Mark with adjacent indicator 'C' and the subject area as shown below which represents that the product has been evaluated by an accredited CB to the applicable CSA Standards respectively.
Product: | Auxiliary, Signalling and Tripping Relays |
---|---|
Model #: | RXKL1; RXMB1; RXMA 1; RXMS 1; RXMA 2; RXMH 2 |
Electrical Ratings: | RXKL 1: 24-250VDC, 24-240VAC, 50-60Hz, 3.5VA/3W, -20 to 55°C
RXMB 1: 24, 48, 110-125, 220-250VDC 115, 127, 230VAC, 50-60Hz, 2VA, -20 to 55°C RXMA 1: 24, 48-55, 110-125, 220-250VDC, 115, 230VAC, 50-60Hz, 1.3W, -20 to 55°C RXMS 1: 24, 48, 110, 125, 220, 250VDC, 24, 48-60, 110-125VAC, 50-60Hz, 3.3W, -20 to 55°C RXMA 2: 24, 48-55, 110-125, 220-250VDC, 2.5W, -20 to 55°C RXMH 2: 24, 48, 110, 125, 220, 250VDC, 110, 120, 127, 220VAC, 50-60Hz, 4.6W, -20 to 55°C |
Standards: | CSA-C22.2 No. 14 - 2018 |
Conditions of Acceptability: | ➢ Not to be used in location classified as hazardous location.
➢ These relays are intended to be installed in the enclosure or panels or in industrial control equipment as per the Canadian electrical code. ➢ The end application shall provide the appropriate degree of protection for these relays as they are intended to be used in indoor environments. ➢ Intended to be used in pollution degree II environment. ➢ Operating altitude: 2000m. |